Post Buying Request
CQB2-125 10kA Miniature Circuit Breaker
CQB2-125 10kA Miniature Circuit Breaker

CQB2-125 10kA Miniature Circuit Breaker

Member Details

Zhejiang Chuangqi Electric Co., Ltd.

Wenzhou,Zhejiang,China

Manufacturer

  • Product Details
  • Company Profile

Single phase and three phase applications ·High breaking capacity up to 10KA ·Overload protection ·Short circuit protection ·Positive isolation Suitable for industrial, commercial, high-rise and civil residences circuit protection.

1 Application

·Single phase and three phase applications

·High breaking capacity up to 10KA

·Overload protection

·Short circuit protection

·Positive isolation

Suitable for industrial, commercial, high-rise and civil residences circuit protection.


 

2 Type designation

Sinoart enterprise content manager system | Sinoart CMS

3 Technical data

Specifications

Rated voltage(V)

AC230V、AC400V

Nominal current (A)

63A、80A、100A、125A

Number of poles

1P 、2P 、3P 、4P

Tripping curvesC、D

Rated short-circuit breaking capacity lcu(A)

10000A

Rated service Short-circuit breaking capacity Ics(A)

7500A

Rated impulse withstand voltage Uimp(V)

4000V

Mechanical life(cycles)

≥8000

Electrical life(cycles)

≥1500
Tripping characteristics

table 2

Protection degree

IP20

Standards

IEC60947-2、GB/T14048.2

Compliant certification

CCC

 

Table2  Tripping characteristics(Reference temp.30℃)

ItemCurveTest current ln(A)Initial statusTime limit for tripping or non-trippingExpected resultRemark
aC、D1.05lnCold1h(ln≤63A)
2h(ln>63A)
Non-trippingCurrent smoothly rises to specified value within 5s
bC、D1.3lnFollowing Item a test  1h(ln≤63A)
  2h(ln>63A)
Tripping
cC、D2lnCold1s<t<300sTripping
dC
D
8ln×80%
12ln×80%
Coldt≤0.2sNon-trippingSwitch on the power supply by closing the auxiliary switch
eC
D
8ln×120%
12ln×120%
Coldt<0.1sTrippingSwitch on the power supply by closing the auxiliary switch

Note: The terminology “Cold ” means that the test is performed at the base calibration temperature with no load prior to the test.
 
4  Order Specifications
Sinoart enterprise content manager system | Sinoart CMS
 
5 cross-sectional area

Rated  current Ie         Copper cross-sectional area (mm2)
50A<in≤63a< td="" style="box-sizing: border-box">16
63A<in≤80a< td="" style="box-sizing: border-box">25
80A<in≤100a< td="" style="box-sizing: border-box">35
100A<in≤125a< td="" style="box-sizing: border-box">50

 

6 Order Specifications
When ordering circuit breakers, the following points should be specified:
A) Product models, such as CQB2-125;
B) Poles of circuit breakers, such as 1P, 2P, 3P, 4P;
C) Types of instantaneous tripping, such as type C and D;
D) Rated current of circuit breakers, such as 63A, 80A, 100A, 125A;
E) Order quantity, e.g. 100 pcs
Purchase order template  

CQB2-125   2P  C/100A   100pcs

7  Dimensions(unit :mm)

Sinoart enterprise content manager system | Sinoart CMS

 

Sinoart enterprise content manager system | Sinoart CMS


Send Inquiry to This Supplier

  • Title
  • From*
  • toYuanzhao Xu
  • Message*
  • Minimum Order Quantity*
  • Unit
  • Verification Code*

ok
x

Confirm
Cancel
x
Sign into your account
Member ID or Email
Join Free